27
Latest score
50%
Pass rate
4
Inspections
10
Critical violations

Location

View this restaurant on the map

Show interactive map

Latest inspection

PASSED
Apr 28, 2026FOLLOW-UP INSPECTION109 days ago

A follow-up inspection was requested on this date by the manager Stanley following the closure of this facility due to a rodent infestation and wastewater discharge: On this date, the following major violations were observed corrected: Closure conditions abated: K23 No rodents, insects, birds, or animals: - The self-inspection checklist was received signed and completed - A pest control service receipt was provided by Banner Pest service indicating no rodent activity was observed for the 4/28/26 service. Overall rodent activity, entry points, and traps did not indicate rodent activity on the pest control report - No additional points of entry were noted - During this visit, no further evidence of rodent activity was observed - Affected areas appear to be clean and were sanitized per the PIC K22 Sewage and wastewater properly disposed: - The clogged floor sink below the servers station was observed able to drain. According to the PIC, the drain was snaked to clear the line. Other sinks in the facility were run and no additional evidence of wastewater back up was observed at this time - Affected areas of the floor appear to be clean and were sanitized per the PIC Violations verified to be in continued compliance: K05 Hands clean, properly washed; gloves used properly: - Observed food workers washing hands with appropriate procedure between tasks, including between garbage handling and food preparation, unprompted by the specialist K06 Adequate handwash facilities supplied, accessible: - All handwashing facilities were observed accessible and with adequate supplies; Locations: Front bar, near warewashing, near back preparation/walk in cooler, restrooms K07 Proper hot and cold holding temperatures: - Food in cold top inserts were measured in compliance and were observed stocked below the fill line. See measured observations K13 Food in good condition, safe, unadulterated - Food in the walk in cooler was observed re-arranged so that raw duck and other raw foods are stored on separate shelves from vegetables and RTE foods in the walk in cooler to prevent cross contamination K14 Food contact surfaces clean, sanitized - The low temperature dishmachine had not been repaired and still cannot provide the required sanitizer concentration, but this unit was not in use at the time of inspection - A food worker set up the three compartment sink to wash rinse and sanitize with 100 ppm chlorine unprompted by the specialist prior to the restart of operation - The food worker was able to correctly verify and test the sanitizer concentration at this time The major violations resulting in closure of the facility have been abated. Facility okay to operate.

Inspection Timeline

Apr 28, 2026Latest
Passed
FOLLOW-UP INSPECTION
Apr 27, 2026
FailedScore: 27/100
ROUTINE INSPECTION
27
Oct 10, 2025
Passed
FOLLOW-UP INSPECTION
Oct 9, 2025
FailedScore: 48/100
ROUTINE INSPECTION
48

Violations Analysis

10
Critical Violations
7 in last 3 inspections
20
Non-Critical
30
Total Violations
Across 4 inspections

Complete inspection history

4 inspections
PassLatest Apr 28, 2026
N/A

FOLLOW-UP INSPECTION

A follow-up inspection was requested on this date by the manager Stanley following the closure of this facility due to a rodent infestation and wastewater discharge: On this date, the following major violations were observed corrected: Closure conditions abated: K23 No rodents, insects, birds, or animals: - The self-inspection checklist was received signed and completed - A pest control service receipt was provided by Banner Pest service indicating no rodent activity was observed for the 4/28/26 service. Overall rodent activity, entry points, and traps did not indicate rodent activity on the pest control report - No additional points of entry were noted - During this visit, no further evidence of rodent activity was observed - Affected areas appear to be clean and were sanitized per the PIC K22 Sewage and wastewater properly disposed: - The clogged floor sink below the servers station was observed able to drain. According to the PIC, the drain was snaked to clear the line. Other sinks in the facility were run and no additional evidence of wastewater back up was observed at this time - Affected areas of the floor appear to be clean and were sanitized per the PIC Violations verified to be in continued compliance: K05 Hands clean, properly washed; gloves used properly: - Observed food workers washing hands with appropriate procedure between tasks, including between garbage handling and food preparation, unprompted by the specialist K06 Adequate handwash facilities supplied, accessible: - All handwashing facilities were observed accessible and with adequate supplies; Locations: Front bar, near warewashing, near back preparation/walk in cooler, restrooms K07 Proper hot and cold holding temperatures: - Food in cold top inserts were measured in compliance and were observed stocked below the fill line. See measured observations K13 Food in good condition, safe, unadulterated - Food in the walk in cooler was observed re-arranged so that raw duck and other raw foods are stored on separate shelves from vegetables and RTE foods in the walk in cooler to prevent cross contamination K14 Food contact surfaces clean, sanitized - The low temperature dishmachine had not been repaired and still cannot provide the required sanitizer concentration, but this unit was not in use at the time of inspection - A food worker set up the three compartment sink to wash rinse and sanitize with 100 ppm chlorine unprompted by the specialist prior to the restart of operation - The food worker was able to correctly verify and test the sanitizer concentration at this time The major violations resulting in closure of the facility have been abated. Facility okay to operate.

No reported violations
Fail Apr 27, 2026
27/100

ROUTINE INSPECTION

This facility shall remain closed until all major violations have been verified corrected by this department. Facility is to immediately cease and desist all operations, including but not limited to food preparation, service, handling, distribution, and sale. Subsequent follow-up inspection after first follow-up shall be billed $298/hour, minimum one hour, during normal business hours (Monday - Friday, 7:30 AM to 4:30 PM), and $645 for a minimum of two hours, during non-business hours, and upon inspector availability. The posted placard is property of the Santa Clara County Department of Environmental Health and shall not be removed, covered-up, relocated, tampered, or copied. Failure to comply may result in enforcement actions per County Ordinance Code Section B11-55. If this facility is found to be in continued operation without a permit may incur a penalty of three (3) times the operating permit fee, and fee(s) for re-inspection(s) charged at the current hourly rate approved by the Santa Clara County Board of Supervisors. Penalties and fees incurred due to enforcement activities must be paid in full prior to the issuance of an operating permit. This inspection was conducted in conjunction with CO0159403

15 reported violations
  • K27: Food separated and protected

    1. Observed vegetables stored below raw duck in the walk in cooler leading to cross contamination of some products. [CA] All food shall be separated and protected from cross-contamination. Store all raw meat or other raw products of animal origin below ready-to-eat food items. [COS] All vegetables not voluntarily discarded were relocated out from below the raw duck 2. Observed a bag of duck heads stored in a bag directly on the floor in the back preparation area adjacent to the preparation sink. [CA] Food shall be stored at least 6 inches above the floor to prevent contamination.

  • K40: Wiping cloths: properly used, stored

    Observed soiled multiuse wiping cloth buckets stored on counter tops throughout the facility, not stored in sanitizer solutions. [CA] Wiping towels shall be stored in sanitizing solution of an approved concentration when not in use (100 ppm - chlorine, 200 ppm - quaternary ammonium).

  • K06: Adequate handwash facilities supplied, accessibleCritical

    1. Observed the rear handwashing sink near the walk in cooler blocked by a tall garbage can and its basin filled with multiuse wiping cloths 2. The basin of the bar handwashing sink was blocked by two chemical spray bottles [CA] Handwashing facility shall be clean, unobstructed, and accessible at all times. 3. Single use paper towels were unavailable for use at the server station hand washing sink. [CA] Single-use sanitary towels shall be provided in dispensers; heated-air hand drying device may be substituted for single-use towels. [COS] 1. The garbage bin and multiuse wiping cloths were relocated 2. The chemical spray bottles were relocated out of the basin 3. Single use paper towels were placed at the servers station.

  • K13: Food in good condition, safe, unadulteratedCritical

    Observed blood from raw duck drip into a container of bok choy and container of cauliflower. [CA] Food is adulterated if it bears or contains any poisonous or deleterious substance that may render it impure or injurious to health and shall be discarded immediately. [COS] Portions of the bokchoy and cauliflower were discarded. Unaffected portions were transferred to a clean container and the original containers were cleaned and sanitized. See VC&D report.

  • K05: Hands clean, properly washed; gloves used properlyCritical

    Observed a food employee pick up vegetables off of the floor to discard and then subsequently wash their hands while gloved. [CA] Properly wash hands with soap, warm water and dry using single use paper towels as required. Gloves shall be properly used and changed when required. [COS] The specialist directed the food employee to remove their gloves and properly and wash their hands and was completed at the back handwashing sink near the walk in cooler.

  • K01: Demonstration of knowledge; food safety certification

    A valid food manager certificate was unavailable for review at the time of inspection. [CA] Food facilities that prepare, handle, or serve non-prepackaged potentially hazard foods shall have a valid Food Safety Certificate available for review at all times.

  • K29: Toxic substances properly identified, stored, used

    Observed an unlabeled spray bottle of water at the back dumpling station. [CA] Chemicals once removed from original container shall be labeled with common name.

  • K22: Sewage and wastewater properly disposedCritical

    The floor sink at the server station was observed clogged and overflowing while running the handwashing sink. [CA] Food facility shall not operate if there is sewage overflowing or backing up in the food facility. The food facility, or impacted areas, shall remain closed until all plumbing problems have been corrected and all contaminated surfaces have been cleaned and sanitized.

  • K23: No rodents, insects, birds, or animalsCritical

    1. Observed fresh rodent droppings at the following locations: - In a bowl in the customer area below a display table - On the 5 bar stools at the bar in the customer area - On the floors behind the cabinet and adjacent to the reach in cooler at the bar - On the floors below the server station - On the lower shelf below the handwashing station at the server station - On the corners of the floors below the handwashing sink adjacent to the three compartment warewashing sink - On the floors around the reach in freezer units in the inoperable walk in freezer 2. Photographs: Taken for documentation purposes. 3. Supervisor Notified: J. Zertuche 4. Notification: The person in charge during inspection, Stanley the manager, has been informed that the facility must close immediately. [CA]: The premises of each food facility must be maintained free of vermin. A facility cannot operate if there is a vermin infestation that leads to contamination of food contact surfaces, packaging, utensils, food equipment, or adulteration of food. The facility is required to cease operations immediately and must remain closed until all corrective actions on the provided checklist are completed. Requirements Before Reopening: 1. Email the signed and completed Reopening Checklist to the assigned inspector. 2. Submit a copy of the pest control report from a licensed provider.

  • K47: Signs posted; last inspection report available

    The current health permit was not posted in a conspicuous location at the time of inspection. [CA] The health permit issued by this department shall be posted in a conspicuous place in the food facility.

  • K34: Warewash facilities: installed/maintained; test strips

    Chlorine test strips for sanitizer were unavailable for use at the time of inspection. [CA] Testing equipment and materials shall be provided to adequately measure the applicable sanitization method used during manual or mechanical warewashing.

  • K14: Food contact surfaces clean, sanitizedCritical

    1. No sanitizer was detected in the final rinse cycle of the low temperature dish machine during active warewashing. [CA] Maintain chlorine in mechanical warewash machine at 50 PPM. [COS/SA] The dishes identified as cleaned on this date were returned to the warewashing area to be cleaned and sanitized. The three compartment sink was set up for manual warewashing at this time with a 100 ppm chlorine sanitizer solution as verified by the specialist. 2. Observed a food worker place a food bin on a garbage can and subsequently place them on cutting boards at the back preparation area on two separate instances. [CA] Maintain food contact surfaces cleaned and sanitized. [COS] The cutting boards were relocated to be cleaned and sanitized at the warewashing sink. The food in containers were relocated to clean containers and returned to storage

  • K07: Proper hot and cold holding temperaturesCritical

    Measured the following items overfilled in the cold top inserts across from the cooks line: - One container of raw chicken at 51F at the top of the unit and 38F at the bottom of the insert - Cooked pork at 52F at the top of container and 39F at the bottom of the insert The PIC stated the foods were placed in the unit approximately 1.25 hours prior. [CA] PHFs shall be held at 41°F or below or at 135°F or above. [COS] The containers were portioned where any part measuring above 41F were relocated to the upright cooler.

  • K41: Plumbing approved, installed, in good repair; proper backflow devices

    Observed a leak below the bar three compartment sink (between left and middle compartments) [CA] Repair plumbing fixture and maintain in clean and good repair.

  • K35: Equipment, utensils: Approved, in good repair, adequate capacity

    Observed the door for the reach in cooler on the opposite side of the cooks line to be unable to fully close. PHF in the unit measured in compliance. The PIC stated the unit recently was unable to maintained shut and a piece of receipt paper is used to friction fit the door closed. [CA] Maintain equipment in good repair and ensure refrigeration is capable to of maintaining PHF at or below 41F.

Pass Oct 10, 2025
N/A

FOLLOW-UP INSPECTION

On site for follow up inspection for routine inspection conducted on 10/09/2025. Facility was closed due to rodent infestation. No rodent activity observed in the facility. Pest control report from 10/10 reviewed. Report identified holes in chemical/supply closet. Door sweep installed under back screen door. Holes identified in small storage closet for chemicals have been sealed. Door sweep installed at storage closet. Facility has been clean and sanitized. No accumulation of food or grease under cook line or warewash area. Continue to maintain facility clean to prevent pest harborage. Per manager, a follow up visit from pest control company is already scheduled and they will continue getting pest control service monthly. Facility is reopened.

No reported violations
Fail Oct 9, 2025
48/100

ROUTINE INSPECTION

CO0158097 Facility is hereby closed due to evidence of rodent infestation. Cease and desist all operations. - Provide pest control report from a licensed pest control company that indicates the type of control measures taken and that the facility has been treated. - Clean and sanitize the affected areas and equipment. - Dispose of all food items that have been adulterated/contaminated. - Seal holes (e.g. in walls and ceilings, repair coved base), and entryways (e.g. weather-stripping around doors); keep exterior doors closed; screen openable windows. - Eliminate food and water sources inside and outside the facility. - Properly store items at least 6 inches above floor in sealed rodent-proof/insect-proof containers; organize overly packed and disorganized storage areas). Please note that pest control treatments for rodents may require a sufficient amount of contact time for these to be effective. Consult with pest control company for guidelines on eliminating harborage, entryways, and food/water sources. Food facility shall remain closed and complete the following requirements before reopening: 1. Email the signed and completed Reopening Checklist to the assigned inspector. 2. Submit a copy of the pest control report from a licensed provider. Contact district specialist Sukhreet Kaur at (408) 918-3460 or sukhreet.kaur@deh.sccgov.org to schedule re inspection once the above requirements are completed. - Subsequent follow-up inspection after first follow-up shall be billed $298/hour, minimum one hour, during normal business hours (Monday - Friday, 7:30 AM to 4:30 PM), and $645, minimum two hours, during non-business hours, and upon inspector availability. - The posted placard is property of the Santa Clara County Department of Environmental Health and shall not be removed, covered-up, relocated, tampered, or copied. Failure to comply may result in enforcement actions per County Ordinance Code Section B11-55. - A facility found to be in continued operation without a permit may incur a penalty of three (3) times the operating permit fee, and fee(s) for re-inspection(s) charged at the current hourly rate approved by the Santa Clara County Board of Supervisors. Penalties and fees incurred due to enforcement activities must be paid in full prior to the issuance of an operating permit

15 reported violations
  • K14: Food contact surfaces clean, sanitized

    Measured chlorine at 0 ppm in dish machine. No active warewashing at the time of the inspection. Use manual warewashing with chlorine sanitizer until dish machine is repaired. [CA] Maintain chlorine in mechanical warewash machine at 50 PPM. Manual warewashing shall be accomplished by using a three-compartment sink where the utensils are first precleaned, washed with hot soapy water, rinsed with hot water, sanitized with an approved method, and air dried. Use 1 TBS of bleach (5.25%) per 1 gal. of water for chlorine solution (100 PPM). Use 1 tbs of quaternary ammonium (10%) per 2 gal. of water for quaternary ammonium (200 PPM).

  • K01: Demonstration of knowledge; food safety certification

    Lack of food manager certificate and food handler cards in the facility. [CA] Food facilities that prepare, handle, or serve non-prepackaged potentially hazard foods shall have a valid Food Safety Certificate available for review at all times. Each food handler shall maintain a valid food handler card for the duration of his or her employment as food handler. A valid food handler card shall be provided within 30 days of after the date of hire.

  • K48: Plan review

    Observed new equipment (double door dryer for duck) in the facility. [CA] Discontinue using the new equipment. Obtain approvals from plan check prior to using the equipment. A person proposing to build or remodel a food facility shall submit plans and specifications for review and shall receive plan approval prior to starting any new construction or remodeling. Contact DEH at 408-918-3400 or at www.ehinfo.org to obtain plan check requirements.

  • K07: Proper hot and cold holding temperaturesCritical

    Measured raw meat (pork, chicken and beef) at 42F in top insert prep unit. [CA] PHFs shall be held at 41°F or below or at 135°F or above. [COS] Per PIC, all the meat was cut and prepared 30 minutes ago and will be used or discarded at the end of lunch shift. Tofu, bean sprouts measured at 45F in single door refrigerator. Per PIC, both items were stored at prep area for use and put back inside the unit 30 minutes ago. [CA] PHFs shall be held at 41°F or below or at 135°F or above. Use only small portions of food during preparation so that it does not exceed the maximum amount of time allowed for diligent prep. Ambient temperature of the unit is above 50F. Measured duck at 54F hanging in duck drying refrigerator unit. Ambient temperature of the unit is above 50F. Per PIC, duck was boiled in water at 11 AM and stored in the unit. Discontinue using this unit to dry/cool duck. [CA] PHFs shall be held at 41°F or below or at 135°F or above. [COS] PIC moved the duck to walk in cooler so it cool downs to 41F.

  • K44: Premises clean, in good repair; Personal/chemical storage; Adequate vermin-proofing

    Observed a gap under back door. Open hole on floor in small storage room for chemicals near walk in cooler. Few small floor areas in the kitchen are open with metal covers. Per PIC, there was a potential leak in the basement so the areas are to check piping. Ensure these are not where rodents are entering the facility from. [CA] Eliminate gap greater than 1/4" to prevent the entrance and harborage of vermin. Back door of the facility propped open. [CA] Keep back door closed at all times to prevent the entrance and harborage of vermin.

  • K33: Nonfood contact surfaces clean

    Accumulation of grease and other debris on pipes under warewash area, poles and pipes in around cookline area. [CA] Nonfood-contact surfaces of equipment shall be kept free of an accumulation of dust, dirt, food residue, and other debris.

  • K23: No rodents, insects, birds, or animalsCritical

    1. Observed Vermin: Documented in the following areas: Multiple rodent droppings in corner next to deep fryer and refrigerator, under cook line Sticky traps and snap traps throughout the kitchen Pest control report dates 10/8/25 indicates major rodent activity with sanitation issues. 2. Photographs: Taken for documentation purposes. 3. Supervisor Notified: Monica Huato 4. Notification: The person in charge during inspection, Stanley, has been informed that the facility must close immediately. [CA]: The premises of each food facility must be maintained free of vermin. A facility cannot operate if there is a vermin infestation that leads to contamination of food contact surfaces, packaging, utensils, food equipment, or adulteration of food. The facility is required to cease operations immediately and must remain closed until all corrective actions on the provided checklist are completed. Requirements Before Reopening: 1. Email the signed and completed Reopening Checklist to the assigned inspector. 2. Submit a copy of the pest control report from a licensed provider.

  • K06: Adequate handwash facilities supplied, accessibleCritical

    Hand wash sink near walk in cooler is obstructed with food boxes in the front and a container in the sink. Hand wash sink near three compartment sink is partially blocked with a pot, rice storage container and a new unit for duck. Paper towel roll is stuck in the dispenser. [CA] Handwashing facility shall be clean, unobstructed, and accessible at all times. Provide single use paper towels in dispenser at all times. [COS] Hand wash sinks made available and paper towels provided.

  • K34: Warewash facilities: installed/maintained; test strips

    Lack of chlorine test strips in the facility. [CA] Provide chlorine test strips.

  • K39: Thermometers provided, accurate

    Lack of thermometers in refrigerator unit. [CA] A thermometer +/- 2°F shall be provided and correctly located in each hot and cold holding unit containing potentially hazardous foods.

  • K30: Food storage: food storage containers identified

    Observed food boxes and containers stored directly on the floor throughout the facility. [CA] Food shall be stored at least 6 inches above the floor to prevent contamination.

  • K05: Hands clean, properly washed; gloves used properly

    Chef using phone with gloves while working at cook line station. When manager told chef to wash hands, chef washed hands with gloves on in three compartment sink at front area. [CA] Properly wash hands with soap, warm water and dry using single use paper towels as required. Single use gloves cannot be rewashed. [COS] Chef removed gloves and wash hands at hand wash sink.

  • K21: Hot and cold water available

    Hot water measured at 112F at three compartment sink. [CA] Hot water shall be supplied at a minimum temperature of at least 120°F measured from the faucet throughout facility except at handwash sinks.

  • K45: Floor, walls, ceilings: built,maintained, clean

    Accumulation of grease and other food debris on floors and under equipment throughout the facility. Observed standing water and food debris under warewash area. [CA] Clean the floors and walls and maintain facility in good condition.

  • K38: Adequate ventilation/lighting; designated areas, use

    Accumulation of grease on filters and panels around the hood. [CA] Clean mechanical exhaust hood and/or filters of grease accumulation.

Source: Santa Clara County open data. Records are supplied as-is and may take 24–48 hours to reflect a newly published inspection.