K41: Plumbing approved, installed, in good repair; proper backflow devices1) Observed the 2 faucets at the 3-compartment sink were loose.
[CA] Repair faucets and maintain in good condition.
2) Under the 3-compartment sink: observed lack of one inch air gap between drain pipe and top of floor sink.
[CA] Maintain a minimum one inch air gap between the drain pipe and the top of the floor sink.
K21: Hot and cold water availableMeasured warm/hot water at the restroom handwash sink and the 1-compartment prep sink (across from the cooking equipment) to be 78F.
[CA] Provide warm water (100F) at the restroom handwash sink, and hot water (120F) at the prep sink.
Note: If the temperature of water provided to a handwashing sink is not readily adjustable at the faucet, the temperature of the water shall be at least 100°F, but not greater than 108°F.